Influence of Cable Length on Short-Circuit Calculations

Influence of Cable Length on Short-Circuit Calculations

Article published in Revista Lumière, semptember 2011 edition, p. 64-78.

Abstract

The objective of this article is to establish a comparison between short-circuit levels in medium and low voltage systems, calculated under different scenarios involving utility contributions and variations in the lengths of power supply cables.

Keywords: Short-Circuit Calculation, Selectivity Study

Introduction

Short-circuit calculations and selectivity studies are fundamental activities in industrial electrical design, especially nowadays, when production systems are increasingly dependent on reliable sources of electrical energy.

An important part of short-circuit calculations is related to the mathematical treatment of power cables, whether medium or low voltage. In practice, it is common to disregard short lengths of cable (or use estimated lengths), based on the belief that they do not significantly impact the calculations. On the other hand, some advocate for maximum precision in measuring all cable lengths, a situation which, in certain cases, may bring unnecessary difficulty to calculations and field data collection without resulting in qualitative improvements in the studies.

In this article, Section 1 presents a brief theoretical discussion on short-circuit calculations. Section 2 addresses a simplified methodology for three-phase short-circuit calculations. Section 3 presents two calculation examples for different points in a theoretical system, powered at 13,800 V with low-voltage panels supplied via transformers. Section 4 explores the influence of cable lengths in the system on short-circuit levels, presenting the results of simulations conducted using PTW software, version 6.5.2.7, Dapper module. Variables include the short-circuit level at the service entrance, the length of the main power supply cables, the length of the transformer supply cables and the length of the low-voltage panel supply cables. Finally, Section 5 highlights the main conclusions of this study.

1. Basic Theory on Short-Circuit Calculations in Industrial Electrical Installations

Short-circuit currents mainly depend on the impedances between the power source and the fault location (busbars, cables, machine terminals). Certain types of loads, such as motors, also contribute to the increase in short-circuit levels. However, their influence is generally much smaller than that of the utility provider. In this article, the influence of motors on short-circuit levels will not be addressed. Thus, the short-circuit is considered solely as a function of the impedances between the utility and the fault point.

According to Mamede Filho (2010), points farther from the generation system are strongly influenced by the impedance of transmission lines, as their impedance is significantly higher than that of generators. Therefore, the short-circuit current consists of two main components, illustrated graphically in Figure 1.1:

  • Symmetrical Component: As the name suggests, this is the symmetrical part of the current, which predominates in the short-circuit after a few cycles.

  • DC Offset Component: This component decreases over time due to the system’s inability to instantly vary magnetic flux.

Forma de onda da corrente durante um curto-circuito

Figure 1.1 – Current waveform during a short-circuit (Source: SKM, 2006a, 2006b)

Simplified Methodology for Three-Phase Short-Circuit Calculation

The most commonly used method for short-circuit calculations in practice is the per-unit system, also known as “pu”. The value of electrical quantities (voltage, current, power, impedance, etc.) is defined as the ratio between the actual value of the quantity and a selected base value.

The main advantage of this method lies in the fact that different voltage levels exist in our circuits due to the presence of transformers. In this way, by using pu values, transformers can be represented by a single impedance as if their turns ratio were 1:1, simplifying the calculations.

To illustrate the studies in this work, all analyses will be based on the theoretical system shown in the diagram of Figure 2.1.

Diagrama Unifilar do sistema

Figure 2.1 – Single-line diagram of the theoretical system to be studied

2.1 Definition of Base Values

Initially, base values must be selected for the per-unit (pu) calculations. Typically, a base power value (Pb) of 100 MVA is used:

Pb = 100 MVA  (2.1)

For the base voltage (Vb), it’s common to use the highest voltage in the system under analysis. In our case, we will work with a system at 13,800 V:

Vb = 13,800 V  (2.2)

From these values, we can calculate the base current (Ib):

Corrente base

2.2 Utility Company Impedance and Short-Circuit Levels

The impedance may be provided directly by the utility in per unit (pu), or if given in Amperes, it must be converted to pu using the equation:

Z₁(pu)₍utility₎ = Ib / Icc₃ø₍sym, utility₎  (2.4)

Where:

  • Icc₃ø₍sym, utility₎ – Symmetrical three-phase short-circuit current at the utility’s point of delivery

  • Ib – Base current

  • Z₁(pu)₍utility₎ – Positive-sequence impedance at the utility’s point of delivery

2.3 Transformer Impedance

Impedância do transformador

Where:

  • Z₁(pu)₍trafo₎, R₁(pu)₍trafo₎, X₁(pu)₍trafo₎ – Positive-sequence impedance, resistance, and inductive reactance of the transformer

  • Z% – Percent impedance of the transformer (nameplate data)

  • Pt – Transformer power (in VA)

  • Pb – Base power (100 MVA)

2.4 Cable Impedance

Impedância dos cabos

  • Cable R, X, Z – Positive-sequence resistance, inductive reactance, and impedance of the cable

  • R per meter and X per meter – Resistance and reactance per meter (manufacturer data)

  • Pb – Base power (100 MVA)

  • V – Nominal voltage of the cable circuit (in Volts)

  • Dist – Distance (in meters)

  • ncpf – Number of cables per phase

2.5 – Three-Phase Short-Circuit Currents

Cálculo da corrente de curto circuito trifásico

  • Icc₃ø₍sym₎ – Symmetrical three-phase short-circuit current

  • Ib – Base current

  • Z(pu) – Equivalent impedance at each point in per unit

  • Icc₃ø₍asym₎ – Asymmetrical three-phase short-circuit current

  • e – Euler’s number (2.71828)

  • π – Pi (3.14159)

  • X/R – Ratio between positive-sequence inductive reactance and resistance at the point of interest

Example of Three-Phase Short-Circuit Calculation

To illustrate the equations presented in Section 2 and validate the effectiveness of the calculations made through simulations using the PTW software version 6.5.2.7, we present the short-circuit level calculations performed for the system shown in Figure 2, considering the data from Tables 3.1 to 3.4.

Table 3.1 – Utility Company Data

Short-Circuit Level at Point of Delivery (A) X/R Ratio
5,000 8

Table 3.2 – Medium Voltage Cable Impedance

Cable Positive-Sequence Resistance per meter (Ω/km) Positive-Sequence Inductive    Reactance per meter (Ω/km)
50mm2 (8.7/15kV) 0.4938 0.1551
35mm2 (8.7/15kV) 0.6684 0.1651
25mm2 (8.7/15kV) 0.9272 0.1726

 

Table 3.3 – Low Voltage Cable Impedance

Cable Positive-Sequence Resistance per meter (Ω/km) Positive-Sequence Inductive    Reactance per meter (Ω/km)
25mm2 (0.6/1kV) 0.9362 0.1150
240mm2 (0.6/1kV) 0.1009 0.0980
185mm2 (0.6/1kV) 0.1303 0.0980

Source: Ficap catalog, Fipex 0.6/1kV cables, single core, installed in trefoil configuration

Table 3.4 – Transformer Data

Transformer Power (kVA) Voltage (V) Percent Impedance (Z%)  Percent Resistance (R%)
TR01 2,000 13,800 – 440/254 6.5% 1.1%
TR02 112.5 13,800 – 220/127 4.49% 2.56%

 

3.1 Calculation of System Impedances in pu

Considering base values of Pb = 100 MVA and Vb = 13,800 V, and applying equation 2.4 to the utility company data (Table 3.1), we obtain the following results (Table 3.5):

Table 3.5 – Utility Company Impedance Values in pu

Positive-Sequence Resistance in pu Positive-Sequence Inductive Reactance in pu
0.103785 0.830278

Applying equation 2.8 to the cables, we get the following results (Table 3.6):

Table 3.6 – Cable Impedance Values in pu

Cables Size / Insulation Distance Cables per phase Positive-Sequence Resistance (pu) Positive-Sequence Inductive Reactance (pu)
Main MV Cable 50mm2 (8.7/15kV) 20 m 1 0.0052 0.0016
MV Cable TR01 35mm2 (8.7/15kV) 20 m 1 0.0070 0.0017
MV Cable TR02 25mm2 (8.7/15kV) 20 m 1 0.0097 0.0018
LV Cable TR01 240mm2 (0.6/1kV) 20 m 8 0.1303 0.1265
LV Cable TR02 185mm2 (0.6/1kV) 20 m 1 5.3843 4.0496

Applying equations 2.5, 2.6, and 2.7 to the transformers, we obtain (Table 3.7):

Table 3.7 – Transformer Impedance Values in pu

Transformer Power (kVA) Voltage (V) Resistance (pu) Inductive Reactance (pu)
TR01 2,000 13,800 – 440/254 0.5500 3.2031
TR02 112.5 13,800 – 220/127 22.7556 32.8000

 

3.2 Calculation of Equivalent Impedances in pu at Several System Points

The equivalent impedance at SE-Main is given by the vector sum of the utility company impedance and the Main MV cable:

ZeqSE-Main = Zutility + Zcable MT Main = 0.103785 + j 0.830278 + 0.0052 + j0.0016 ZeqSE-Main = 0.108985 + j0.831878 pu ZeqSE-Main = 0.8390 pu (angle = 82.53o)

Using equations 2.11 and 2.12, we get the short-circuit values for SE-Main :

Icc3øsym SE-Main = 4,183.70 / 0.8390 = 4,986A Icc3øasym SE-Main = 6,834A

The equivalent impedance at the primary of TR01 (SE-TR01) is the sum of the utility impedance, Main MV cable, and MV cable TR01:

ZeqSE-TR01 = Zutility + Zcable MT Main + Zcable MT TR01 = 0.103785 + j 0.830278 + 0.0052 + j0.0016 + 0.0070 + j0.0017 ZeqSE-TR0l = 0.115985 + j0.833578 pu ZeqSE-TR0l = 0.8417 pu (angle = 82.07o)

Using equations 2.11 and 2.12, we obtain short-circuit for SE TR-01:

Icc3øsym SE-TR01 = 4,183.70 / 0.8417 = 4,971 A Icc3øasym SE-TR01 = 6,732 A

For the other points of the system, similar calculations are made. The results are presented in Table 3.8, which shows the symmetrical and asymmetrical three-phase short-circuit levels. For low-voltage points, the levels have already been calculated using the nominal voltage of each panel.

Table 3.8 – Calculated Three-Phase Short-Circuit Levels

Input Voltage (V) Zeq (pu) Icc3øsym (A) X/R ratio: Icc3øasym (A)
Entrada Consumidor 13800 0.8367 5000 8 6914
SE Geral 13800 0.8390 4986 7.63 6834
SE TR01 13800 0.8417 4971 7.19 6732
SE TR02 13800 0.8421 4968 7.02 6698
PGBT-01 440 4.2388 30956 5.23 39173
PGBT-02 220 47.1018 5572 1.33 5621
CCM01 440 4.8518 27045 3.54 31304
CCM02 440 5.4926 23890 2.81 26329
CCM03 440 6.1524 21327 2.41 22843
CCM04 440 6.8259 19223 2.15 20228
QLF01 220 79.2611 3311 0.63 3311
QLF02 220 115.6912 2268 0.45 2268
QLF03 220 153.3784 1711 0.36 1711

 

4. Analysis of the Influence of Medium and Low Voltage Cable Lengths on Short-Circuit Calculations

In order to analyze the variations in short-circuit levels based on different cable lengths and entry short-circuit levels, 150 different simulations were carried out, as follows:

  • For each entry three-phase symmetrical short-circuit level of 3,000 A, 4,000 A, 5,000 A, 6,000 A, and 7,000 A, the following simulations were performed:
  • Varying the length of the Main MV Cable (0, 20, 40, 60, 80, 100, 120, 140, 160, 180, and 200 m)

  • Varying the lengths of MV TR01 and TR02 Cables (same intervals)

  • Varying the lengths of LV TR01 and TR02 Cables (same intervals)

Simplified Table 4.1 presents the scenarios in which the simulations were conducted:

Symmetrical Three-Phase Short Circuit Level at the Input Point
Cable 3,000 A 4,000 A 5,000 A 6,000 A 7,000 A
Cable MT Main 10 scenarios 10 scenarios 10 scenarios 10 scenarios 10 scenarios
Cable MT TR 02 10 scenarios 10 scenarios 10 scenarios 10 scenarios 10 scenarios
Cable BT TR 01 10 scenarios 10 scenarios 10 scenarios 10 scenarios 10 scenarios
Cable BT TR 02 10 scenarios 10 scenarios 10 scenarios 10 scenarios 10 scenarios

Cable sizing is not under discussion in this work, only its influence on short-circuit calculations. Therefore, voltage drop levels under normal operating conditions were not considered.

4.1 Analysis of Short-Circuit Levels by Varying the Length of the Main MV Cable

After simulating the scenarios involving various entry short-circuit levels and variations in the Main MV cable, the results are presented in Figures 4.1 to 4.5.

Nível de curto circuito trifásico simétrico variando comprimento do cabo

Figure 4.1 – Three-phase symmetrical short-circuit levels at the Main Substation as a function of the symmetrical short-circuit at the Consumer Input for 3 lengths of the Main MV cable. The graph shows variations in short-circuit levels between 1% (Icc = 3000 A) and 2.44% (Icc = 7000 A) for every 100 m of cable.

Nível de curto circuito trifásico no TR1

Figure 4.2 – Symmetrical three-phase short-circuit levels in SE TR01 as a function of the symmetrical three-phase short-circuit at the Consumer Input for 3 lengths of Main MV cable.

Nível de curto circuito trifásico no TR2

Figure 4.3 – Symmetrical three-phase short-circuit levels in SE TR02 as a function of the symmetrical three-phase short-circuit at the Consumer Input for 3 lengths of Main MV cable. In the same way as in figure 4.1, figures 4.2 and 4.3 show that variations in the length of the input cable cause variations in the short-circuit levels between 0.97% (input Icc = 3000A) and 2.48% (input Icc = 7000A) for every 100 m.

Nível de curto circuito trifásico no PGBT1

Figure 4.4 – Symmetrical three-phase short-circuit levels in PGBT01 as a function of the symmetrical three-phase short-circuit at the Consumer Input for 3 lengths of Main MV cable.

Figure 4.4 shows that variations in the length of the input cable cause variations in the short-circuit levels in PGBT01 between 0.32% (input Icc = 3000A) and 0.39% (input Icc = 7000A) for every 100 m.

Nível de curto circuito trifásico no PGBT2

Figure 4.5 – Symmetrical three-phase short-circuit levels in PGBT02 as a function of the symmetrical three-phase short-circuit at the Consumer Input for 3 lengths of Main MT cable.

Figure 4.5 shows that variations in the length of the input cable cause variations in the short-circuit levels in PGBT02 between 0.05% (input Icc = 3000A) and 0.07% (input Icc = 7000A) for every 100 m.

4.2 Analysis of Short-Circuit Levels by Varying the Length of the Cable MT TR01

In a similar manner to that presented in item 4.1, simulations were carried out by varying the length of the MT TR01 cable for different input short-circuit levels and the results are presented below in figures 4.6 and 4.7.

Nível de curto circuito trifásico no TR1 variando cabo TR01

Figure 4.6 – Symmetrical three-phase short-circuit levels at SE TR01 as a function of the symmetrical three-phase short-circuit at the Consumer Input for 3 lengths of MT TR01 cable. In the graph in figure 4.6, it can be seen that variations in the length of the MT TR01 cable cause variations in the short-circuit levels between 1.14% (input Icc = 3000A) and 2.99% (input Icc = 7000A) for every 100 m, a value very close to that verified in graphs 4.1, 4.2 and 4.3.

Nível de curto circuito trifásico no PGBT1 variando alimentação TR01

Figure 4.7 – Symmetrical three-phase short-circuit levels in PGBT01 as a function of the symmetrical three-phase short-circuit at the Consumer Input for 3 lengths of MT TR01 cable. In the graph in figure 4.7, variations in the length of the MT TR01 cable cause variations in the short-circuit levels between 0.34% (input Icc = 3000A) and 0.46% (input Icc = 7000A) for every 100 m, a value very close to that verified in figure 4.4.

 

4.3 Analysis of Short-Circuit Levels by Varying the Length of the Cable MT TR02

At this stage of the work, simulations were carried out by varying the length of the MT TR02 cable for different input short-circuit levels and the results are presented below in figures 4.8 and 4.9.

Nível de curto circuito trifásico no TR2 variando cabo TR02

Figure 4.8 – Symmetrical three-phase short-circuit levels at SE TR02 as a function of the symmetrical three-phase short-circuit at the Consumer Input for 3 lengths of MT TR02 cable. In figure 4.8, it can be seen that variations in the length of the MT TR02 cable cause variations in the short-circuit levels between 1.37% (input Icc = 3000A) and 3.81% (input Icc = 7000A) for every 100 m, a value very close to that seen in graphs 4.1, 4.2, 4.3 and 4.6.

Nível de curto circuito trifásico no PGBT2 variando alimentação TR02

Figure 4.9 – Symmetrical three-phase short-circuit levels in PGBT02 as a function of the symmetrical three-phase short-circuit at the Consumer Input for 3 lengths of the MT TR02 cable. In the graph in figure 4.7, variations in the length of the MT TR01 cable cause variations in the short-circuit levels between 0.09% (input Icc = 3000A) and 0.11% (input Icc = 7000A) for every 100 m, a value very close to that verified in figure 4.5.

4.4 Analysis of Short-Circuit Levels by Varying the Length of the Cable BT TR01

At this stage of the simulations, the length of the BT TR01 cables was varied for different input short-circuit levels and the results are presented below in figure 4.10.

Nível de curto circuito trifásico no PGBT1 variando cabo TR01

Figure 4.10 – Symmetrical three-phase short-circuit levels in PGBT01 as a function of the symmetrical three-phase short-circuit at the Consumer Input for 10 lengths of the LV TR01 cable. In the graph in Figure 4.10, variations in the length of the LV TR01 cable cause variations in the short-circuit levels between 15.34% (input Icc = 3000A) and 19.29% (input Icc = 7000A) for every 100 m, a value much higher than those verified in the simulations where the medium voltage cables were varied.

4.5 Analysis of Short-Circuit Levels by Varying the Length of the Cable BT TR02

In the last stage of the simulations, the length of the LV TR02 cables was varied for different input short-circuit levels and the results are shown below in figure 4.11.

Nível de curto circuito trifásico no PGBT2 variando cabo TR02

Figure 4.11 – Symmetrical three-phase short-circuit levels in PGBT02 as a function of the symmetrical three-phase short-circuit at the Consumer Input for 10 lengths of the LV TR02 cable. In the graph in Figure 4.11, variations in the length of the LV TR02 cable cause variations in the short-circuit levels between 37.26% (input Icc = 3000A) and 49.27% ​​(input Icc = 7000A) for every 100 m, a value much higher than that verified in the simulations where the medium voltage cables were varied.

It can also be seen in Figure 4.11 that the short-circuit is practically independent of the short-circuit level of the consumer input, being subject only to the impedances of the cable and the transformer, since such impedances are much higher than that of the utility.

Conclusion

By grouping the results obtained after the simulations, we have the values ​​according to table 5.1.

Table 5.1 – Variation of the levels of symmetrical three-phase short-circuit for each 100m of cable

Symmetrical Three-Phase Short Circuit % Variation for Every 100m of Cable
Cable SE-Main SE-TR01 SE-TR02 PGBT01 PGBT02
MT-Main 1.00% to 2.44% 0.97% to 2.48% 0.97% to 2.48% 0.32% to 0.39% 0.05% to 0.07%
MT-TR01 1.14% to 2.99% 0.34% to 0.46%
MT-TR02 1.37% to 3.81% 0.09% to 0.11%
BT-TR01 15.34% to 19.29%
BT-TR02 37.26% to 49.27%

In general, it can be concluded that variations in the lengths of supply cables are much more significant in low voltage systems when compared to variations in medium voltage cables.

A more detailed analysis of the results obtained from varying the length of medium voltage cables shows variations between 0.05% and 3.81%, with the first value found at PGBT02 when varying the Main MV cable with an entry short-circuit current (Icc) of 3,000 A, and the second at SE-TR02, varying the MV-TR02 cable with an entry Icc of 7,000 A.

From this data, a comparative analysis can be made between the variations in short-circuit levels caused by medium voltage cables and the accuracy of current transformers used for protection (which is generally 10%). Therefore, it can be assumed that variations of up to 100 meters in medium voltage cables represent relatively insignificant changes in calculations, and it is up to the designer to decide whether or not to consider them in their studies.

On the other hand, the simulations carried out by varying the length of low voltage cables show variations between 15.34% and 49.27% in short-circuit levels. Specifically, 15.34% was calculated for PGBT01 with 100-meter variations of the LV-TR01 cable and an entry Icc of 3,000 A, and 49.27% at PGBT02 for 100-meter variations of the LV-TR02 cable with an entry Icc of 7,000 A.

Thus, it can be concluded that the correct specification of the characteristics and length of low voltage cables is crucial for obtaining reliable short-circuit calculation results, with particular emphasis on the cables between transformers and the main low voltage panels.

The correct determination of short-circuit levels in low voltage is closely linked to selectivity studies, especially regarding the settings of medium voltage protection devices (relays), which are typically configured so that their instantaneous protections operate for values higher than the highest asymmetric short-circuit levels present in the low voltage system.

If the short-circuit values in the low voltage system are not correctly calculated, the designer may be mistakenly led to set medium voltage relays to values that are too low, compromising selectivity, or to values that are too high, causing short-circuits (between transformer LV terminals and the main panel incoming terminals) to be detected only by the time-delayed protections of the medium voltage relays.

Bibliography

J. Mamede Filho, Instalações Elétricas Industriais, Rio de Janeiro, LTC, 2010

SKM Systems Analysis, Inc. Power Tools for Windows – A Fault Reference Manual – Electrical Engineering Analysis Software for Windows, Manhattan, USA, SKM, 2006a.

SKM Systems Analysis, Inc. Power Tools for Windows – A Fault Reference Manual – Electrical Engineering Analysis Software for Windows, Manhattan, USA, SKM, 2006b.

Principais questões relacionadas a este artigo:

  • How to calculate a short-circuit?
  • How to calculate a three-phase short-circuit?
  • How to calculate a phase-to-ground short-circuit?
  • How to calculate a single-phase short-circuit?
  • Formulas for calculating short-circuits.
  • Calculation of three-phase short-circuits.
  • Calculation of symmetrical short-circuits.
  • Calculation of asymmetrical short-circuits.
  • Calculation of impedances in pu.

For more articles, click here

Sem Comentários

Poste um Comentário